Removing the combi-sensor (overheating sensor /
flame sensor)
Remove the
AIRTRONIC
cover (see fig. 1)
Remove the controller (see fig. 2)
Disconnect both connectors of the cable harness combi-
sensor from the controller.
Unlock clip from combi-sensor.
Remove combi-sensor.
Fig. 5
Cable harness combi-sensor
Clip
Checking the combi-sensor
Observe a max. temperature of 320 °C for checking
the combi-sensor.
Overheating sensor
Check the overheating sensor with a digital multimeter.
If the resistance value is outside the set point indicated in
the values table, then the combi-sensor must be replaced.
Flame sensor
Check the flame sensor with a digital multimeter.
If the resistance value is outside the set point indicated in
the values table, then the combi-sensor must be replaced.
Temperature (°C)
Resistance (Ohm)
Resistance (kOhm)
Temperature (°C)
2400
2200
2000
1800
1600
1400
1200
1000
800
40 0 50 100 150 200 250 300 350
1800
1600
1200
1000
800
600
400
200
0
40
2000
20
0
20
40
60
80
100
120
140
200
Values table overheating sensor
Temperature °C Resistance kW min. max.
- 40 1597.00 1913.00
- 20 458.80 533.40
0 154.70 175.50
20 59.30 65.84
40 25.02 28.04
60 11.56 13.16
80 5.782 6.678
100 3.095 3.623
120 1.757 2.081
140 1.050 1.256
160 0.6554 0.792
180 0.4253 0.5187
200 0.2857 0.3513
Values table flame sensor
Temperature °C Resistance W min. max.
- 40 825.90 859.60
0 980.00 1020.00
40 1132.30 1178.50
80 1282.80 1335.10
120 1431.50 1489.90
160 1578.30 1642.80
200 1723.40 1793.70
240 1866.60 1942.80
280 2008.10 2090.00
320 2147.70 2235.40
360 2285.50 2378.80
400 2421.50 2520.30